Technical Features

SMARTCONTROL I/O24 + LON SMARTCONTROL IP65 / 24 V= SMARTCONTROL Modbus TCP SMARTCONTROL LON SMARTCONTROL SMARTCONTROL I/O24
Item number U300F U300C U300G U300E U300A U300D
Product details page Details Details Details Details Details Details
Number 8 (IS0 ... IS7) 2, up to 2 analog inputs can be reconfigured to relay outputs (jumper series JP6) 1 (FTT-10, 2-wire twisted-pair) Max. 4 8 (T0 to T7) 8 (O0 ... O7) Max. 24 (DI0 ... DI23) Max. 2 8 (IS0 ... IS7) 2, up to 2 analog inputs can be reconfigured to relay outputs (jumper series JP6) 8 (O0 ... O7) 8 (IS0 ... IS7) 2, up to 2 analog inputs can be reconfigured to relay outputs (jumper series JP6) 8 (O0 ... O7) 8 (IS0 ... IS7) 2, up to 2 analog inputs can be reconfigured to relay outputs (jumper series JP6) 1 (FTT-10, 2-wire twisted-pair) 8 (O0 ... O7) 8 (IS0 ... IS7) 2, up to 2 analog inputs can be reconfigured to relay outputs (jumper series JP6) 8 (O0 ... O7) 8 (IS0 ... IS7) 2, up to 2 analog inputs can be reconfigured to relay outputs (jumper series JP6) Max. 4 8 (T0 to T7) 8 (O0 ... O7) Max. 24 (DI0 ... DI23) Max. 2
Chapter08 Backup battery - I/O module for 24 channels Backup battery - I/O module for 24 channels
Electrical isolation Active operating mode: electrically isolated, passive operating mode: not electrically isolated Common ground
No electrical isolation
No connection to frame ground
SMARTCONTROL may be accept external voltage.
Active operating mode: electrically isolated, passive operating mode: not electrically isolated Common ground
No electrical isolation
No connection to frame ground
SMARTCONTROL may be accept external voltage.
Active operating mode: electrically isolated, passive operating mode: not electrically isolated Common ground
No electrical isolation
No connection to frame ground
SMARTCONTROL may be accept external voltage.
Active operating mode: electrically isolated, passive operating mode: not electrically isolated Common ground
No electrical isolation
No connection to frame ground
SMARTCONTROL may be accept external voltage.
Active operating mode: electrically isolated, passive operating mode: not electrically isolated Common ground
No electrical isolation
No connection to frame ground
SMARTCONTROL may be accept external voltage.
Active operating mode: electrically isolated, passive operating mode: not electrically isolated Common ground
No electrical isolation
No connection to frame ground
SMARTCONTROL may be accept external voltage.
Cable length Max. 200 m Max. 200 m Max. 200 m Max. 200 m Max. 200 m Max. 200 m
Function Connection of measuring transducers such as pressure, humidity, and temperature sensors etc. Read-out of energy and consumption meters with M-Bus interface. Slot for M-Bus level converter Control via program, timer, peak load management Control of fieldbus devices with RS�485 interface and Modbus protocol, e.g. the A2000 power meter from GMC-I Messtechnik GmbH. Insertion of an analog, ISDN, GSM or Bluetooth modem from the range of accessory products. Control via program, timer, peak load management Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Read-out and parameters configuration of SMARTCONTROL Meter or status output, for example current, gas, water and heat meters, as well as door and window contacts Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Connection of measuring transducers such as pressure, humidity, and temperature sensors etc. Read-out of energy and consumption meters with M-Bus interface. Slot for M-Bus level converter Control via program, timer, peak load management Control of fieldbus devices with RS�485 interface and Modbus protocol, e.g. the A2000 power meter from GMC-I Messtechnik GmbH. Insertion of an analog, ISDN, GSM or Bluetooth modem from the range of accessory products. Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Read-out and parameters configuration of SMARTCONTROL Meter or status output, for example current, gas, water and heat meters, as well as door and window contacts Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Connection of measuring transducers such as pressure, humidity, and temperature sensors etc. Read-out of energy and consumption meters with M-Bus interface. Slot for M-Bus level converter Control via program, timer, peak load management Control of fieldbus devices with RS�485 interface and Modbus protocol, e.g. the A2000 power meter from GMC-I Messtechnik GmbH. Insertion of an analog, ISDN, GSM or Bluetooth modem from the range of accessory products. Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Read-out and parameters configuration of SMARTCONTROL Meter or status output, for example current, gas, water and heat meters, as well as door and window contacts Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Connection of measuring transducers such as pressure, humidity, and temperature sensors etc. Read-out of energy and consumption meters with M-Bus interface. Slot for M-Bus level converter Control via program, timer, peak load management Control of fieldbus devices with RS�485 interface and Modbus protocol, e.g. the A2000 power meter from GMC-I Messtechnik GmbH. Insertion of an analog, ISDN, GSM or Bluetooth modem from the range of accessory products. Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Read-out and parameters configuration of SMARTCONTROL Meter or status output, for example current, gas, water and heat meters, as well as door and window contacts Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Connection of measuring transducers such as pressure, humidity, and temperature sensors etc. Read-out of energy and consumption meters with M-Bus interface. Slot for M-Bus level converter Control via program, timer, peak load management Control of fieldbus devices with RS�485 interface and Modbus protocol, e.g. the A2000 power meter from GMC-I Messtechnik GmbH. Insertion of an analog, ISDN, GSM or Bluetooth modem from the range of accessory products. Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Read-out and parameters configuration of SMARTCONTROL Meter or status output, for example current, gas, water and heat meters, as well as door and window contacts Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Connection of measuring transducers such as pressure, humidity, and temperature sensors etc. Read-out of energy and consumption meters with M-Bus interface. Slot for M-Bus level converter Control via program, timer, peak load management Control of fieldbus devices with RS�485 interface and Modbus protocol, e.g. the A2000 power meter from GMC-I Messtechnik GmbH. Insertion of an analog, ISDN, GSM or Bluetooth modem from the range of accessory products. Control via program, timer, peak load management Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems. Read-out and parameters configuration of SMARTCONTROL Meter or status output, for example current, gas, water and heat meters, as well as door and window contacts Control of fieldbus devices with RS�232 interface or external interface converter for other bus systems.
Protocol TCP/IP Connection of Modbus devices and devices compatible with the ASCII protocol M bus per EN 1434-3 TCP/IP Connection of Modbus devices and devices compatible with the ASCII protocol M bus per EN 1434-3 TCP/IP Connection of Modbus devices and devices compatible with the ASCII protocol M bus per EN 1434-3 TCP/IP Connection of Modbus devices and devices compatible with the ASCII protocol M bus per EN 1434-3 TCP/IP Connection of Modbus devices and devices compatible with the ASCII protocol M bus per EN 1434-3 TCP/IP Connection of Modbus devices and devices compatible with the ASCII protocol M bus per EN 1434-3
Chapter10 RS232 interface (field 1) RS232 interface (field 1) RS232 interface (field 1) RS232 interface (field 1) RS232 interface (field 1) RS232 interface (field 1)
Lithium cell CR 2032 3 V, for maintaining meter readings in the event of power failure CR 2032 3 V, 230 mAh, for retaining date and time CR 2032 3 V, 230 mAh, for retaining date and time CR 2032 3 V, 230 mAh, for retaining date and time CR 2032 3 V, 230 mAh, for retaining date and time CR 2032 3 V, for maintaining meter readings in the event of power failure CR 2032 3 V, 230 mAh, for retaining date and time
Calibration Default setting: 0 and 100 °C to ±0,05 °C Default setting: ±0,005 V at 10 V Default setting: ±0,005 V at 10 V Default setting: ±0,005 V at 10 V Default setting: ±0,005 V at 10 V Default setting: ±0,005 V at 10 V Default setting: 0 and 100 °C to ±0,05 °C Default setting: ±0,005 V at 10 V
Exclusion Not simultaneously with RS 485 (Modbus) Not simultaneously with RS 232 (field 1) Not simultaneously with RS 485 (Modbus) Not simultaneously with RS 232 (field 1) Not simultaneously with RS 485 (Modbus) Not simultaneously with RS 232 (field 1) Not simultaneously with RS 485 (Modbus) Not simultaneously with RS 232 (field 1) Not simultaneously with RS 485 (Modbus) Not simultaneously with RS 232 (field 1) Not simultaneously with RS 485 (Modbus) Not simultaneously with RS 232 (field 1)
Input quantity PT1000 platinum sensor with 2-wire technology PT1000 platinum sensor with 2-wire technology
Chapter04 Digital inputs - standard Digital inputs - SMARTCONTROL I/O module for 24 channels Digital inputs - standard Digital inputs - standard Digital inputs - standard Digital inputs - standard Digital inputs - standard Digital inputs - SMARTCONTROL I/O module for 24 channels
Chapter13 Two RS485/1 and RS485/2 interfaces (Modbus) (as of SMARTCONTROL V3) Two RS485/1 and RS485/2 interfaces (Modbus) (as of SMARTCONTROL V3) Two RS485/1 and RS485/2 interfaces (Modbus) (as of SMARTCONTROL V3) Two RS485/1 and RS485/2 interfaces (Modbus) (as of SMARTCONTROL V3) Two RS485/1 and RS485/2 interfaces (Modbus) (as of SMARTCONTROL V3) Two RS485/1 and RS485/2 interfaces (Modbus) (as of SMARTCONTROL V3)
Operating condition 5 ... 50 °C, no condensation 5 ... 50 °C, no condensation 5 ... 50 °C, no condensation 5 ... 50 °C, no condensation 5 ... 50 °C, no condensation 5 ... 50 °C, no condensation
Inputs assignable as status inputs 8, e.g. door contact, motion detector 8, e.g. door contact, motion detector 8, e.g. door contact, motion detector 8, e.g. door contact, motion detector 8, e.g. door contact, motion detector 8, e.g. door contact, motion detector
Contact load 15 mA with input voltage of 12 V= or 24 V= 15 mA with input voltage of 12 V= or 24 V= 15 mA with input voltage of 12 V= or 24 V= 15 mA with input voltage of 12 V= or 24 V= 15 mA with input voltage of 12 V= or 24 V= 15 mA with input voltage of 12 V= or 24 V=
Pulse sequence At least 10 ms / 10 ms (0/1) At least 10 ms / 10 ms (0/1) At least 10 ms / 10 ms (0/1) At least 10 ms / 10 ms (0/1) At least 10 ms / 10 ms (0/1) At least 10 ms / 10 ms (0/1)
IP address Static or dynamic via DHCP server, factory setting: 192.168.130.190 Static or dynamic via DHCP server, factory setting: 192.168.130.190 Static or dynamic via DHCP server, factory setting: 192.168.130.190 Static or dynamic via DHCP server, factory setting: 192.168.130.190 Static or dynamic via DHCP server, factory setting: 192.168.130.190 Static or dynamic via DHCP server, factory setting: 192.168.130.190
Non-operation / extended storage periods Replace once every 2 years Replace once every 2 years Replace once every 2 years Replace once every 2 years Replace once every 2 years Replace once every 2 years Replace once every 2 years
Programming Graphically via function blocks with the SMARTCONTROL manager
Each channel separately
Graphically via function blocks with the SMARTCONTROL manager
Each channel separately
Graphically via function blocks with the SMARTCONTROL manager
Each channel separately
Graphically via function blocks with the SMARTCONTROL manager
Each channel separately
Graphically via function blocks with the SMARTCONTROL manager
Each channel separately
Chapter11 RS232 interface (field 2) RS232 interface (field 2) RS232 interface (field 2) RS232 interface (field 2) RS232 interface (field 2) RS232 interface (field 2)
Chapter06 Switching output (semiconductor relay) - standard Switching output - SMARTCONTROL I/O module for 24 channels Switching output (semiconductor relay) - standard Switching output (semiconductor relay) - standard Switching output (semiconductor relay) - standard Switching output (semiconductor relay) - standard Switching output (semiconductor relay) - standard Switching output - SMARTCONTROL I/O module for 24 channels
System monitoring Watchdog timer Watchdog timer Watchdog timer Watchdog timer Watchdog timer Watchdog timer
Switching voltage Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads Max. 40 V =/~, no inductive loads
Switching current Max. 1 A Max. 1 A Max. 1 A Max. 1 A Max. 1 A Max. 1 A Max. 1 A Max. 1 A
Switching alternative Can be plugged in via jumper as an alternative to digital inputs (DI18 ... DI21). Analog inputs A6, A7 or switching outputs K1, K2 As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Switching outputs K1, K2 or analog inputs A6, A7
Can be plugged in via jumper as an alternative to digital inputs (DI22 ... DI23). Analog inputs A6, A7 or switching outputs K1, K2 As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Switching outputs K1, K2 or analog inputs A6, A7
Analog inputs A6, A7 or switching outputs K1, K2 As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Switching outputs K1, K2 or analog inputs A6, A7
Analog inputs A6, A7 or switching outputs K1, K2 As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Switching outputs K1, K2 or analog inputs A6, A7
Analog inputs A6, A7 or switching outputs K1, K2 As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Switching outputs K1, K2 or analog inputs A6, A7
Can be plugged in via jumper as an alternative to digital inputs (DI18 ... DI21). Analog inputs A6, A7 or switching outputs K1, K2 As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Switching outputs K1, K2 or analog inputs A6, A7
Can be plugged in via jumper as an alternative to digital inputs (DI22 ... DI23).
Bus termination Internal, 110 Ohm, can be connected via jumper Internal, 110 Ohm, can be connected via jumper Internal, 110 Ohm, can be connected via jumper Internal, 110 Ohm, can be connected via jumper Internal, 110 Ohm, can be connected via jumper Internal, 110 Ohm, can be connected via jumper
Measuring range 0…1 V
0…10 V
0…20 mA or 4…20 mA
0…5 V
0…1 V
0…10 V
0…20 mA or 4…20 mA
0…5 V
0…1 V
0…10 V
0…20 mA or 4…20 mA
0…5 V
0…1 V
0…10 V
0…20 mA or 4…20 mA
0…5 V
0…1 V
0…10 V
0…20 mA or 4…20 mA
0…5 V
0…1 V
0…10 V
0…20 mA or 4…20 mA
0…5 V
Chapter07 Analog output - SMARTCONTROL I/O module for 24 channels Analog output - SMARTCONTROL I/O module for 24 channels
Inputs assignable as synchronization input 1 (IS7)
The clock is synchronized to the next quarter hour.
1 (IS7)
The clock is synchronized to the next quarter hour.
1 (IS7)
The clock is synchronized to the next quarter hour.
1 (IS7)
The clock is synchronized to the next quarter hour.
1 (IS7)
The clock is synchronized to the next quarter hour.
1 (IS7)
The clock is synchronized to the next quarter hour.
Data rate 10/100 MBit 10/100 MBit 10/100 MBit 10/100 MBit 10/100 MBit 10/100 MBit
Active signals Max. 24 V=
Min. 12 mA
Min. 12 V
Max. 24 V=
Min. 12 mA
Min. 12 V
Max. 24 V=
Min. 12 mA
Min. 12 V
Max. 24 V=
Min. 12 mA
Min. 12 V
Max. 24 V=
Min. 12 mA
Min. 12 V
Max. 24 V=
Min. 12 mA
Min. 12 V
Accuracy classes temperature sensor Class 1/3 B: dT = ±1/3 x (0,30 °C + 0,005 x T)
Class A: dT = ±(0,15 °C + 0,002 x T)
Class B: dT = ±(0,30 °C + 0,005 x T)
Class 1/3 B: dT = ±1/3 x (0,30 °C + 0,005 x T)
Class A: dT = ±(0,15 °C + 0,002 x T)
Class B: dT = ±(0,30 °C + 0,005 x T)
Optical pulse display LED on the PCB LED on the PCB LED on the PCB LED on the PCB LED on the PCB LED on the PCB
Baud rate 2400, 4800, 9600 or 19200 baud 300, 2400 or 9600 baud 2400, 4800, 9600 or 19200 baud 300, 2400 or 9600 baud 2400, 4800, 9600 or 19200 baud 300, 2400 or 9600 baud 2400, 4800, 9600 or 19200 baud 300, 2400 or 9600 baud 2400, 4800, 9600 or 19200 baud 300, 2400 or 9600 baud 2400, 4800, 9600 or 19200 baud 300, 2400 or 9600 baud
Storage rules Cyclical or based on conditions Cyclical or based on conditions Cyclical or based on conditions Cyclical or based on conditions Cyclical or based on conditions Cyclical or based on conditions
Switching element Semiconductor relay (photo MOS) Semiconductor relay (photo MOS) Semiconductor relay (photo MOS) Semiconductor relay (photo MOS) Semiconductor relay (photo MOS) Semiconductor relay (photo MOS) Semiconductor relay (photo MOS) Semiconductor relay (photo MOS)
Output current 0 - 20 0 - 20
Units M-Bus protocol M-Bus protocol M-Bus protocol M-Bus protocol M-Bus protocol M-Bus protocol
Resolution 12-bit A-D converter Better than 0.05 K 0.0000 01 12-bit A-D converter 0.0000 01 12-bit A-D converter 0.0000 01 12-bit A-D converter 0.0000 01 12-bit A-D converter 0.0000 01 12-bit A-D converter Better than 0.05 K 0.0000 01
Chapter12 Ethernet interface Ethernet interface Ethernet interface Ethernet interface Ethernet interface Ethernet interface
GSM Connection to the GSM radio network. Contract with network service provider and enabled SIM card required. Good reception must be assured at the installation site. The SMS function is supported by SMARTCONTROL. Connection to the GSM radio network. Contract with network service provider and enabled SIM card required. Good reception must be assured at the installation site. The SMS function is supported by SMARTCONTROL. Connection to the GSM radio network. Contract with network service provider and enabled SIM card required. Good reception must be assured at the installation site. The SMS function is supported by SMARTCONTROL. Connection to the GSM radio network. Contract with network service provider and enabled SIM card required. Good reception must be assured at the installation site. The SMS function is supported by SMARTCONTROL. Connection to the GSM radio network. Contract with network service provider and enabled SIM card required. Good reception must be assured at the installation site. The SMS function is supported by SMARTCONTROL. Connection to the GSM radio network. Contract with network service provider and enabled SIM card required. Good reception must be assured at the installation site. The SMS function is supported by SMARTCONTROL.
Output voltage 0 - 10 0 - 10
Detection method Interrupt Interrupt Interrupt Interrupt Interrupt Interrupt
Memory expansion Formatting via SMARTCONTROL manager
Internal slot for microSD card
Optional 2 GB microSD card
Formatting via SMARTCONTROL manager
Internal slot for microSD card
Optional 2 GB microSD card
Formatting via SMARTCONTROL manager
Internal slot for microSD card
Optional 2 GB microSD card
Formatting via SMARTCONTROL manager
Internal slot for microSD card
Optional 2 GB microSD card
Formatting via SMARTCONTROL manager
Internal slot for microSD card
Optional 2 GB microSD card
Formatting via SMARTCONTROL manager
Internal slot for microSD card
Optional 2 GB microSD card
Inputs assignable as tariff inputs 3 (IS1, IS3 and IS5), the respective upstream inputs (IS0, IS2, IS4) are counted. 3 (IS1, IS3 and IS5), the respective upstream inputs (IS0, IS2, IS4) are counted. 3 (IS1, IS3 and IS5), the respective upstream inputs (IS0, IS2, IS4) are counted. 3 (IS1, IS3 and IS5), the respective upstream inputs (IS0, IS2, IS4) are counted. 3 (IS1, IS3 and IS5), the respective upstream inputs (IS0, IS2, IS4) are counted. 3 (IS1, IS3 and IS5), the respective upstream inputs (IS0, IS2, IS4) are counted.
Chapter05 Temperature input (PT1000) Temperature input (PT1000)
Continuous operation Replace once every 5 years Replace once every 5 years Replace once every 5 years Replace once every 5 years Replace once every 5 years Replace once every 5 years Replace once every 5 years
Edge slope Any Any Any Any Any Any
Number of participants 480 250 480 250 480 250 480 250 480 250 480 250
Chapter15 Modem slot Modem slot Modem slot Modem slot Modem slot Modem slot
Frequency Max. 50 Hz Max. 1 Hz Max. 50 Hz Max. 50 Hz Max. 50 Hz Max. 50 Hz Max. 50 Hz Max. 1 Hz
Accuracy of temperature measurement Better thanr ±0,5 °C (depending on sensor�s DIN class) Better thanr ±0,5 °C (depending on sensor�s DIN class)
Chapter03 Analog inputs Analog inputs Analog inputs Analog inputs Analog inputs Analog inputs
Protection circuitry Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks Suppressor diodes for voltage peaks
Switching alternatives As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
As an alternative to the digital inputs (DI22 ... DI23), an analog output can be plugged in via jumper.
As an alternative to the digital inputs (DI18 ... DI21), a switching output can be plugged in via jumper.
Chapter01 System data System data System data System data System data System data
Socket connector RJ45, pin assignments selectable via jumper RJ45, pin assignments selectable via jumper RJ45, pin assignments selectable via jumper RJ45, pin assignments selectable via jumper RJ45, pin assignments selectable via jumper RJ45, pin assignments selectable via jumper
Accuracy Better than ±0,02 V Better than ±0,02 V Better than ±0,02 V Better than ±0,02 V Better than ±0,02 V Better than ±0,02 V Better than ±0,02 V Better than ±0,02 V
Saving of meter readings Every 15 minutes Every 15 minutes Every 15 minutes Every 15 minutes Every 15 minutes Every 15 minutes
Recording frequency Max 1/s Max. 1/s Max 1/s Max. 1/s Max 1/s Max. 1/s Max 1/s Max. 1/s Max 1/s Max. 1/s Max 1/s Max 1/s Max. 1/s Max 1/s
Internal resistance Voltage measurement: 200 kOhm
Current measurement: 249 ?
Voltage measurement: 200 kOhm
Current measurement: 249 ?
Voltage measurement: 200 kOhm
Current measurement: 249 ?
Voltage measurement: 200 kOhm
Current measurement: 249 ?
Voltage measurement: 200 kOhm
Current measurement: 249 ?
Voltage measurement: 200 kOhm
Current measurement: 249 ?
Time base Battery-backed real-time clock Battery-backed real-time clock Battery-backed real-time clock Battery-backed real-time clock Battery-backed real-time clock Battery-backed real-time clock
Operation mode Active
Passive
Selectable via internal jumper (JP2)
LonTalk protocol (CSMA) Active
Passive
Selectable via internal jumper (JP2)
Active
Passive
Selectable via internal jumper (JP2)
Active
Passive
Selectable via internal jumper (JP2)
LonTalk protocol (CSMA) Active
Passive
Selectable via internal jumper (JP2)
Active
Passive
Selectable via internal jumper (JP2)
Power supply SMARTCONTROL can be operated with 12 ... 24 V DC.
Power consumption *:
– Basic PCB < 2.5 W
– Interface module add-on for LON: max. 1 W additional
– I/O module add-on for 24 channels: max. 10 W additional
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 V DC
Optional: external power pack (primary switched-mode)
Built-in power pack
– Basic PCB < 2.5 W
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 or 24 V DC depending on variant
SMARTCONTROL can be operated with 12 ... 24 V DC.
Power consumption *:
– Basic PCB < 2.5 W
– Interface module add-on for LON: max. 1 W additional
– I/O module add-on for 24 channels: max. 10 W additional
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 or 24 V DC depending on variant
SMARTCONTROL can be operated with 12 ... 24 V DC.
Power consumption *:
– Basic PCB < 2.5 W
– Interface module add-on for LON: max. 1 W additional
– I/O module add-on for 24 channels: max. 10 W additional
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 V DC
Optional: external power pack (primary switched-mode)
SMARTCONTROL can be operated with 12 ... 24 V DC.
Power consumption *:
– Basic PCB < 2.5 W
– Interface module add-on for LON: max. 1 W additional
– I/O module add-on for 24 channels: max. 10 W additional
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 or 24 V DC depending on variant
SMARTCONTROL can be operated with 12 ... 24 V DC.
Power consumption *:
– Basic PCB < 2.5 W
– Interface module add-on for LON: max. 1 W additional
– I/O module add-on for 24 channels: max. 10 W additional
Input: 100 ... 240 V AC, 50 ... 60 Hz
Output: 12 V DC
Optional: external power pack (primary switched-mode)
Inputs assignable as pulse inputs 8, e.g. meter with pulse input 8, e.g. meter with pulse input 8, e.g. meter with pulse input 8, e.g. meter with pulse input 8, e.g. meter with pulse input 8, e.g. meter with pulse input
Chapter02 SMARTCONTROL - standard
SMARTCONTROL - interface module for LON
SMARTCONTROL - I/O module for 24 channels
SMARTCONTROL - IP 65 control cabinet variant SMARTCONTROL - standard SMARTCONTROL - standard
SMARTCONTROL - interface module for LON
SMARTCONTROL - standard SMARTCONTROL - standard
SMARTCONTROL - I/O module for 24 channels
Chapter14 LON interface (interface module for LON) LON interface (interface module for LON)
Dimensions (W x H x D) 128 x 56 mm
216 x 96 mm
226 x 210 x 70 mm
380 x 380 x 210 mm 226 x 210 x 70 mm 128 x 56 mm 226 x 210 x 70 mm 216 x 96 mm
Temperature measuring range -50°C - 170°C -50°C - 170°C
Chapter16 Modems (optional) Modems (optional) Modems (optional) Modems (optional) Modems (optional) Modems (optional)
Model Electrically isolated Electrically isolated (NC, floating) Common ground Electrically isolated Electrically isolated Electrically isolated Electrically isolated Electrically isolated Electrically isolated (NC, floating) Common ground
ISDN Connection to public digital telephone lines via RJ45 connector socket and ISDN-S0 bus. Connection to public digital telephone lines via RJ45 connector socket and ISDN-S0 bus. Connection to public digital telephone lines via RJ45 connector socket and ISDN-S0 bus. Connection to public digital telephone lines via RJ45 connector socket and ISDN-S0 bus. Connection to public digital telephone lines via RJ45 connector socket and ISDN-S0 bus. Connection to public digital telephone lines via RJ45 connector socket and ISDN-S0 bus.
Calculations Limit value monitoring
Integral value generation
Mean value generation
Calculator
Heating and cooling quantities
Timer programs
Limit value monitoring
Integral value generation
Mean value generation
Calculator
Heating and cooling quantities
Timer programs
Limit value monitoring
Integral value generation
Mean value generation
Calculator
Heating and cooling quantities
Timer programs
Limit value monitoring
Integral value generation
Mean value generation
Calculator
Heating and cooling quantities
Timer programs
Limit value monitoring
Integral value generation
Mean value generation
Calculator
Heating and cooling quantities
Timer programs
Limit value monitoring
Integral value generation
Mean value generation
Calculator
Heating and cooling quantities
Timer programs
Storage depth 2 MB flash ring buffer 2 MB flash ring buffer 2 MB flash ring buffer 2 MB flash ring buffer 2 MB flash ring buffer 2 MB flash ring buffer
Weight 1.5kg 10kg 1.5kg 1.5kg 1.5kg 1.5kg
Debouncing Digital filter, 5 ms Digital filter, 5 ms Digital filter, 5 ms Digital filter, 5 ms Digital filter, 5 ms Digital filter, 5 ms
Topology (cable type: Belden 85102, ? 1.3 mm, 28 /Km)
Bus, terminated: ? 2700 m
Free topology:  500 m
(cable type: Belden 85102, ? 1.3 mm, 28 /Km)
Bus, terminated: ? 2700 m
Free topology:  500 m
Chapter09 RS232 interface (M-Bus) RS232 interface (M-Bus) RS232 interface (M-Bus) RS232 interface (M-Bus) RS232 interface (M-Bus) RS232 interface (M-Bus)
Mounting type Screw mounted Screw mounted Screw mounted Screw mounted Screw mounted Screw mounted
Status display 1 LON LED active 1 LON LED active
Resolution of AD converter 12-bit 12-bit
Transmission speed 78 kbps 78 kbps
Control buttons F1
Reset on the system PCB
F1
Reset on the system PCB
F1
Reset on the system PCB
F1
Reset on the system PCB
F1
Reset on the system PCB
F1
Reset on the system PCB
Power consumption Approx. 10 W Approx. 1 W Approx. 10 W
Connection elements Plug strip with screw connector (up to 63 users per station) Plug strip with screw connector (up to 63 users per station)
Analogue Connection to public analog telephone lines, also with PBX systems. Connection to public analog telephone lines, also with PBX systems. Connection to public analog telephone lines, also with PBX systems. Connection to public analog telephone lines, also with PBX systems. Connection to public analog telephone lines, also with PBX systems. Connection to public analog telephone lines, also with PBX systems.
Safety Protected with selectable password Second password for read access only Protected with selectable password Second password for read access only Protected with selectable password Second password for read access only Protected with selectable password Second password for read access only Protected with selectable password Second password for read access only Protected with selectable password Second password for read access only
Operating voltage 3.3 V or 5.0 V, can be selected with jumper 3.3 V or 5.0 V, can be selected with jumper 3.3 V or 5.0 V, can be selected with jumper 3.3 V or 5.0 V, can be selected with jumper 3.3 V or 5.0 V, can be selected with jumper 3.3 V or 5.0 V, can be selected with jumper
Max. meter reading 9999 9999, 9999 99 9999 9999, 9999 99 9999 9999, 9999 99 9999 9999, 9999 99 9999 9999, 9999 99 9999 9999, 9999 99
Degree of protection (IP) IP20 IP65 IP20 IP20 IP20 IP20
Material housing Metal Metal Metal Metal Metal Plastic